LPG Nozzle Glossary: Terms Used in GG20 Documentation
Short answer: Short definitions of the terms used across GasGuard GG20 documentation, from 1¾" ACME and nozzle reach to release volume, nose piece types, reed switches, safety breaks and UL 125.
- 1¾" ACME
- The threaded LPG fill connection common on North American forklift cylinders, RVs and older autogas vehicles. The GG20's connector nut screws onto it.
- Nozzle reach
- Length of the connector nut. 160 mm on the GG20, 125 mm on the GG1.
- Nose piece
- The sealing front of the valve. Single ('E'), hybrid ('H') or dual ('DN') on GasGuard ACME nozzles.
- Dual nose piece
- ELAFLEX's patented design that seals to the fill point even if the nozzle isn't fully tightened. Used on the GG20DN.
- Release volume
- LPG vented when the nozzle is disconnected: the liquid trapped between nozzle valve and fill valve. 1.7 to 1.9 cm³ on the GG20 range.
- Low-emission connector
- Under South Coast AQMD Rule 1177, a connector releasing no more than 4 cm³ on disconnect.
- Inlet swivel
- The rotating joint where the hose attaches. ½" or ¾" NPT female on the GG20.
- NPT
- National Pipe Taper, the US tapered pipe thread standard.
- Strainer
- 300 µm / 50 mesh screen inside the nozzle that stops debris from upstream.
- Hold-open latch
- A catch that holds the lever open. Optional (L) and not UL listed on the GG20.
- Reed switch / magnet
- Some dispensers start the pump when a magnet in the nozzle guard leaves a reed switch in the boot. Order option J for these.
- Nozzle boot (NB-GG)
- The enclosed holster for GasGuard nozzles on the dispenser.
- Safety break / pull-away (ARK 19)
- A coupling in the hose that separates and seals if a vehicle drives off while connected.
- UL 125
- The Underwriters Laboratories standard covering flow control valves for anhydrous ammonia and LP-gas, under which the GG20 is listed.
- NFPA 58
- The Liquefied Petroleum Gas Code published by the National Fire Protection Association, adopted by most US states.
- AHJ
- Authority having jurisdiction: the agency or official who approves an installation.
- K15 / Euro connector
- Push-to-connect LPG filler adopted under NFPA 58 for new vehicles. Served by the GG40 or ZVG 2, not the GG20.
Sources
- GasGuard Information 2.15: GG20 nozzle range (ELAFLEX, Oct 2015)
- GasGuard Information 6.15: part number breakdown (ELAFLEX)
- South Coast AQMD Rule 1177, LPG transfer and dispensing
- The ins and outs of autogas dispensers (Butane-Propane News)