GG20 Troubleshooting: Leaks, Hard Connections, No Flow, Stiff Lever

Updated 2026-10-07 · Sourced from ELAFLEX documentation

Short answer: A small gas release on disconnect is normal (1.7 to 1.9 cm³). A continuous leak is not: release the lever, hit the emergency stop, clear the area and take the nozzle out of service. If the nozzle won't thread on smoothly, disconnect and retry; never force it, and check for a damaged or worn fill point. Low or no flow usually means the coupling isn't fully engaged, a clogged strainer, or a dispenser issue. A pump that won't start on a reed-switch dispenser points to a missing J magnet.
SymptomLikely causeWhat to do
Short hiss when unscrewingNormal release of trapped liquid between nozzle and fill valveNothing. Keep hands clear of the coupling.
Continuous or uncontrolled gas releaseDamaged seal, worn nose piece, damaged fill valveRelease the lever, press the emergency stop, clear the area. Trained personnel inspect the nozzle and the receptacle. Isolate the nozzle if it recurs.
Nut won't thread on smoothlyMisalignment, cross-threading, dirty or damaged ACME thread on the fill pointDisconnect and reconnect square to the valve. Never force it. Inspect both threads.
Leak at the inlet swivelSwivel seals worn, grub screw looseOut of service. Swivel seals are part of the 6 to 12 month inspection and the 24-month seal kit.
No flow with lever pulledNozzle not fully coupled (the valve won't open uncoupled), pump not runningCheck the nut is fully tightened and the dispenser is running.
Flow lower than usualClogged strainer, pump or hose restriction, adapter in lineHave the strainer inspected and cleaned or replaced (EK172.1). Remove adaptors if fitted.
Pump doesn't start when nozzle liftedReed-switch boot but nozzle has no magnetFit the J magnet option (GGJ assembly) or change the dispenser setting.
Lever hard to holdNormal for single nose piece; or worn lever/valve partsConsider the GG20H or GG20DN, which have lower lever force. If force has increased over time, inspect the valve.
Connector nut won't turn freelyDirt, worn pawl or springClean; have the pawl and spring checked at inspection.

Rows on "flow lower than usual" and "lever hard to hold" combine ELAFLEX's component descriptions with common service practice; they are not listed word for word in the manual. Everything involving a leak follows the manual's stop-and-isolate instruction.

Quick answers

My GG20 leaks continuously, what should I do?
Release the lever, press the dispenser emergency stop, clear the area, and take the nozzle out of service for inspection by trained personnel.

Sources

  1. Installation and Operating Manual, GG1 & GG20 series (ELAFLEX PACIFIC, 5/2016)
  2. GG20 Repair & Maintenance Manual (ELAFLEX PACIFIC / L.G. Equipment)